Fan Coil Unit Power Cleansing & Progressive Filtration Strategy
Background
A commercial building operating underfloor heating and fan coil units began experiencing significant cooling performance issues. The heating side of the system remained stable, however the cooling element, delivered via fan coil units (FCUs) was underperforming.
Our onsite investigation identified widespread internal blockages within the FCUs caused by circulating debris, scale, and suspended magnetite. Restricted flow through the coils was preventing effective heat exchange and reducing cooling output across the building.
A full system cleanse was not required at this stage, as the issue was isolated to the cooling circuit and fan coil units.
The Challenge
- FCUs not delivering required cooling output
- Internal blockages restricting circulation
- Suspended debris and magnetite contamination
- Risk of repeated recontamination
- Limited site access (works required out of hours)
- No desire for full system shutdown
The Solution
Targeted Power Cleansing
Each fan coil unit was manually unblocked and power cleansed using our PackaPUMP system to individually:
- Restore circulation
- Improve cooling transfer efficiency
- Reduce strain on pumps and system components
- Reinstate reliable cooling performance
This controlled approach restored system functionality without unnecessary disruption to the heating circuit, this was only achieved by our own bespoke filtration units.
Replacement of Dosing Pot with SludgeBuster™ Smiddy
The existing dosing pot was removed and replaced with a SludgeBuster™ Smiddy filtration unit.
The Smiddy now acts as:
- The primary cleaning and dosing point
- A continuous magnetic debris capture unit
- A fine bag filtration system down to 0.5 micron
By installing the Smiddy:
- Circulating sludge and magnetite are continuously removed
- Heat exchangers and system components gain ongoing protection
- System pressure monitored by BMS integration.
Key Takeaways for Similar Buildings
If you are experiencing:
- Fan coil units not delivering cooling
- Uneven temperature across zones
- Repeated blockages
- High pump strain or pressure drops
- Dirty water samples
- Systems that cannot be fully shut down
Then a targeted FCU cleanse combined with progressive inline filtration will be the correct solution — not a full disruptive system strip-down.
Why This Strategy Works
✔ Restores flow without full system shutdown
✔ Removes contamination in stages
✔ Protects pumps and exchangers
✔ Reduces future callouts
✔ Prevents rapid recontamination
✔ Improves occupant comfort
✔ Strengthens long-term system stability
Without on-going filtration and treatment following cleansing, systems with historic contamination issues will almost always re-contaminate.