One Filter That Fits Them All
Inline Filtration:
Full-Flow System Protection
Inline installation places the MagBag directly in the main flow path, typically between key components like the boiler, pump sets, or critical heat exchangers. All flow passes through the filter, offering continuous, full-system protection.
When to Use It:
- New installs or major refurbishments where flow rates and pipe sizes can be planned around the unit.
- Systems with known high sludge content that require proactive filtration.
- Applications where downstream components (e.g. plate heat exchangers) need safeguarding from debris damage.
Typical Positioning:
- Between boiler headers and system flow/return.
- Directly upstream of sensitive equipment (plate exchangers, chillers, etc.).
- Always allow clearance above the unit for bag changes and cleaning access.
Best Practice Tips:
- Size the MagBag to suit your peak flow rate, always refer to the flow performance chart.
- Use isolation valves either side of the unit to enable safe servicing.
- If your system runs variable speed pumps, consider choosing a higher-micron bag to prevent flow restriction during ramp-up.
- Ensure magnetic basket is always installed when running inline, this is your first line of defence against iron oxide particles.
Side-Stream Filtration:
Continuous Cleaning Without Interrupting Flow
Side-stream installation connects the MagBag off the main pipework, typically drawing 5–15% of total system volume at a time. Over time, this continuously polishes the water, gradually removing debris without disrupting main flow operation.
When to Use It:
- On live systems that cannot be shut down for inline integration.
- In retrofit jobs where pipework constraints prevent inline installation.
- Where continuous cleaning is needed over long periods (e.g. under commissioning or handover phase).
Typical Positioning:
- Across flow and return legs using a dedicated side-stream pump.
- Off secondary circuit headers.
- Parallel to chilled water loops or underfloor manifolds.
Best Practice Tips:
- Install a small, efficient circulation pump to maintain steady flow across the MagBag.
- Monitor bag loading regularly, especially in dirty systems, side-stream doesn’t mean low-impact.
- For commissioning, use lower micron bags (e.g. 1 or 0.5 micron) to capture fine magnetite and biofilm.
- Use flow restrictors or balancing valves to maintain optimal side-stream draw rate.
Multi-Use
Ready by Design
Every MAGBAG™ unit comes equipped with multi-use auxiliary ports as standard, blanked off for convenience, but ready when you need them. Whether you’re working on a commercial project with Building Management System (BMS) integration or just want to keep a closer eye on system performance, MAGBAG™ makes it easy.
What You Can Connect:
- BMS-Compatible Pressure Sensors – Monitor live system conditions remotely, ideal for facilities teams or smart building setups.
- Differential Pressure Gauges – Keep track of filter loading and plan servicing before issues arise.
- Demineralisation or Conditioning Units – Tie in additional water treatment equipment without pipework alterations.
Why It Matters?
Integrated ports mean built-in flexibility. Whether you’re retrofitting system monitoring or preparing for future upgrades, there’s no need for extra drilling, pipework modifications, or awkward workarounds. It’s all ready from day one – saving time on site and preserving the integrity of the unit.
Ready when you are. No special kits. No fuss.
5 Star Rated
We work hard to deliver top customer service every time.
Customer
"Used MagBag on a commercial heating system with ongoing iron issues. The magnetic capture combined with bag filtration works brilliantly."
★★★★★
Customer
"Used inline and side-stream across different sites. The flexibility is a real advantage and makes system protection much easier."
★★★★★
Customer
"Straightforward to install, easy to service, and built properly. The option to add bag filtration when needed makes it far more useful than standard magnetic filters."
★★★★★
Customer
"Fitted MagBag inline on the flow to protect fan coil units that couldn’t be flushed due to a large biomass plant and buffer vessel that couldn’t be shut down quickly. It’s done exactly what we needed, capturing debris and preventing ongoing blockages."
★★★★★
Customer
"We chose MagBag for its versatility. We use it to protect key components such as heat exchangers. When on site, we fit a bag to restrict flow slightly and strip out the iron, then remove it and run magnet-only inline. Absolutely spot on."
★★★★★
Ready To Improve System Performance Where It Matters?
Contact us to discuss how our HVAC filtration solutions can improve system performance and protection.